Starting ACS355 drives for PROFINET
1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter 98.02
COMM PROT SEL to EXT FBA.
3. Set the FENA configuration parameters in group 51. At the minimum, set parameters 51.01 FBA A
type as Ethernet, 51.02 Protocol/Profile as PNIO ABB Pro (11), 51.04 IP configuration as Static, and
required IP address from parameter 51.05 to parameter 51.08 and 51.09 Subnet CDR as 24.
4. Select how the drive reacts to a fieldbus communication break with parameter 30.18 COMM FAULT
FUNC.
5. Define the time between communication break detection and the selected action with parameter
30.19 COMM FAULT TIME.
6. Define the process data transferred to and from the drive in the FBA-01 configuration parameter
groups 54 and 55.
Note: The adapter module sets the Status word and actual value automatically in parameters 54.01
and 54.02, and Control word and reference in parameters 55.01 and 55.02.
7. Validate the settings made in parameter groups 51, 54 and 55 by setting parameter 51.27 FBA PAR
REFRESH to REFRESH.
8. Set the relevant drive control parameters to control the drive according to the application.