EasyManuals Logo
Home>ABB>Controller>ACSM1 Series

ABB ACSM1 Series User Manual

ABB ACSM1 Series
139 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
ACS580 Minimum required parameter settings for PROFINET
The minimum required parameter settings based on factory default settings.
Parameter
Description
Setting
Comment
50.01
FBA A Enable
Enable
Activates fieldbus module
51.01
FBA A ype
Ethernet
Filedbus type
51.02
Protocol/Profile
PNIO ABB Pro (11)
Communication profile ABB drives
51.04
IP Configuration
Static (0)
-
51.05 ...
51.08
IP address
192.xxx.xx.xx or
any other required
IP address.
-
51.09
Subnet CDR
24
24 For subnet mask 255.255.255.0
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 51 to 55)
52.02
FBA data in2
Act1 16bit (5)
Actual speed as Data Word 2 from the drive
53.02
FBA data out2
Ref1 16bit (2)
Speed reference as Data Word 2 to the drive
20.01
Ext 1 commands
Fieldbus A
Fieldbus interface as source for start and stop
22.11
Ext1 speed ref1
FB A ref1
Fieldbus interface as source for speed
reference
31.11
Fault reset
selection
P.06.01 bit 7
Fieldbus interface as source for fault reset
(46.01)
Speed scaling
[Scale max]
Max speed/frequency scaling value (used in
function block/visualization input
SPEED_REF_MAX). Must be less or equal to
drive parameter max speed/frequency.