E1SL 15 532258 04 - Rev. E
Translation of the original instructions
EN GL IS H
6 BASIC Programming
BASIC Function
Default
][
Simply Connect If you wish to enable Simply Connect, select a channel (CH).
0 = Simply Connect NON enabled, 1 = CH 1, 2 = CH 2, 3 = CH 3, 4 = CH 4
0
CF
Automation model Set the model installed.
Note: whenever the parameter
CF is modified, the relative DEFAULT 1 values are loaded on parameter dF.
no
no = no selection (factory default)
1 = A1000
2 = A1400 AIR
3 = RKE 1400 (for SLIDING FHE )
4 = SF1400
5 = GBF1500
dF
DEFAULT configuration Allows the default programming specific for the Model of the automation to be loaded. It also indicates
whether the programming corresponds with the default parameters.
1 = DEFAULT 1 - standard configuration - Note: whenever parameter CF is modified, the relative DEFAULT 1 values are loaded.
2 = DEFAULT 2 - battery-powered standard configuration, with pre-set tests. The BATTERY KIT must be connected.
no = the programming in progress does not correspond to a DEFAULT configuration (at least 1 parameter modified). Select the cor-
responding value if you wish to reload a DEFAULT program.
Y
Ln
Leaf number - displayed only for SF1400 (
CF= 4) If modified you have to perform the SETUP.
1 = 1 leaf, 2 = 2 leaves
2
Lt
Select passage opening - displayed only for SF1400 (
CF= 4)
1 = narrow opening width: max 65 cm (with 1 leaf), max 130 cm (with 2 leaves)
2 = average opening width: 65…75 cm (with 1 leaf), 130…150 cm (with 2 leaves)
3 = wide opening width: greater than 75 cm (with 1 leaf), greater than 150 cm (with 2 leaves)
2
rM
Direction of rotation of the motor If it is modified you have to perform the SETUP.
1 = STANDARD rotation, -1 = NON STANDARD rotation
1
PO
Partial Open - NOT displayed for SF1400 (
CF= 4) or for GBF1500 (CF= 5)
no = 100%
20… 95 % Adjustment step = 5%
50
PA
Pause time before closing again in automatic operation mode
0… 30 s Adjustment step = 1 s
2
ES
Energy Saving
no = not enabled , Y = enabled
no
Pn
Night pause time In Night mode, after being opened via the Key command, the door remains open for the length of time set (
0 s
…
4.0 min)
0 … 58 s Adjustment step = 2 s
1.0…4.0 min Adjustment step = 10 s (e.g. 1.2 = 1 min and 20 s)
10
cS
Closing speed
level
1… 10
5
1 (if cF=4)
oS
Opening speed
level
1… 10
10 (if cF=1
8
(if cF=2, 3)
5 (if cF=4)
3 (if cF=5)
cF
Closing force level
1… 10
5
oF
Opening force level
1… 10
8
10
(if cF=3)
5 (if cF=5)
tF
Force time on obstacle for CF and OF
0.1… 3.0 s Adjustment step = 0.1 s
1.0
2.0 (if cF=3)
dr
Deceleration ramp when OP and CL
level
1… 10
6
4 (if cF=4)
5 (if cF=5)
Ar
Acceleration ramp when OP and CL
level
1… 10
8
5 (if cF=3, 5)