5–94 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
INPUTS CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Remote Inputs
Remote inputs provide a means of exchanging digital state information between Ethernet-
networked devices supporting IEC 61850. Remote inputs that create FlexLogic operands at
the receiving relay are extracted from GOOSE messages originating in remote devices.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a
specific remote device for local use. The programming is performed by the three settings
shown in the Virtual Inputs section.
Path: Setpoints > Inputs > Remote Inputs
NAME
Range: Up to 13 Alphanumeric Characters
Default: VI 1
An alphanumeric name may be assigned to a Remote Input for diagnostic, setting, and
event recording purposes.
EVENTS
Range: Enabled, Disabled
Default: Enabled
This setting enables event generation whenever Remote Input Status is updated.