10–2 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SUMMARY CHAPTER 10: STATUS
Summary
Configurable SLD
The status of each SLD screen is displayed under Status > Summary > Configurable SLDs
> SLD1(X).
Figure 10-2: Sample SLD
Path: Status > Summary > Configurable SLDs > SLD 1(X)
Once in the SLD screen, by default no breaker/switch is highlighted or selected. Pressing
the Up/Dn (or Up/Dn/Left/Right) navigation keys highlights BKR1 and navigates through
BKR1, 2, 3, etc. and then through Switch1, 2, 3, etc.
If the Up/Dn/Left/Right keys are used, the selection moves to the closest available breaker/
switch from the currently highlighted object. To select the breaker/switch, press the enter
key. Upon pressing the Enter key, the tab labels change to the programmable tab
pushbutton labels and a flash message for the breaker selected appears (Flash Message:
“BKR1 Selected”). Pressing Escape de-selects the breaker/switch and the tab pushbutton
labels.
Annunciator
The graphical annunciator panel emulates a physical annunciator panel. Indicators on the
graphical panel are backlit and have a description of the alarm condition that lights each
indicator. The annunciator panel status window shows the alarms that are active.
To reset an active alarm, first highlight the active alarm using the navigation keys, then
press the reset button to reset the highlighted alarm. If no indicator is selected, all alarms
on the page are reset by pushing the reset button.