10–16 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTORECLOSE CHAPTER 10: STATUS
Autoreclose
It should be noted that the TOTAL SHOT COUNT and SHOT CNT LAST RST D/T are stored in
non-volatile memory, which can be restored after reboot. All statuses can be cleared by
the command in
RECORDS > CLEAR RECORDS > AUTORECLOSE 1(X).
Path: Status > Autoreclose 1(X)
Shot Number in Effect
Range: 0 to 65535 in steps of 1
The present shot number which the Autoreclose scheme is using is displayed in the
SHOT NUMBER IN EFFECT value. If the scheme has reached Lockout, the display is the
shot number after which a Trip caused Lockout.
Shots Remaining
Range: 0 to 65535 in steps of 1
The SHOTS REMAINING value displays the number of reclose shots that can still be
performed. The value displayed is contained in the Shot Limit memory. Each time a
reclose shot is performed, in a given sequence, this Shot Limit is reduced by one. The
Shot Limit can also be reduced to any given value less than the programmed value by
the current supervision function or by user setting (AR1 Reduce Maximum to 1, 2 or 3).
Shot Rate per Hour
Range: 0 to 65535 sh/hrin steps of 1
The number of reclosures in the past hour is shown in the SHOT RATE PER HOUR value.
Shot Cnt Last Rst D/T
Range: MM/DD/YY HH:MM
Default: 01/01/08 00:00:00
The TOTAL SHOT COUNT value shows the total number of reclosures since the SHOT CNT
LAST RST D/T.