7. C300 Controller Operation
7.7. Initiating Synchronization command
7.7
Initiating Synchronization command
To initiate a synchronization command manually to a redundant C300 Controller pair,
perform the following steps.
Prerequisites
You can view active redundant C300 Controller pair on the Monitoring tab in Control
Builder.
Commanding synchronization
In the Monitoring tab, double-click the primary C300 icon to The Parameters
configuration form appears.
Click the Redundancy tab.
Click Enable Synchronization.
Click Yes to confirm the action and issue the synchronize command.
Confirm that the Auto Synchronization State becomes ENABLED and
confirm that sync cycles in the primary C300 Controller's 4-character display.
Click OK to close the Parameters form.
This completes the procedure.