Commissioning
Configuring the digital inputs and outputs
Digital inputs for communication via the MotionBus (CAN) X4
6
141
EDBCSXM064 EN 11.0
6.12.1 Digital inputs for communication via the MotionBus (CAN) X4
Setting C4011 = 0:
Terminal Function Level Response
X6/DI1 Quick stop (QSP)
LOW The drive is decelerated to standstill within the deceleration
time set in C0105.
HIGH The motor follows the setpoint selection.
X6/DI2 Reference switch/
Touch probe sensor
LOW No response
HIGH Activation of reference switch/touch probe sensor (both edge
active)
X6/DI3 Positive hardware limit
switch
LOW The controller reports the activation of the positive hardware
limit switch to the control. A further safety measure can be
implemented by wiring the emergency−off circuit.
HIGH No response
X6/DI4 Negative hardware limit
switch
LOW The controller reports the activation of the negative
hardware limit switch to the control. A further safety
measure can be implemented by wiring the emergency−off
circuit.
HIGH No response
6.12.2 Digital inputs for communication via the automation interface (AIF) X1
Setting C4011 = 1:
Terminal Function Level Response
X6/DI1 Sync source
LOW No sync
HIGH Sync is active
X6/DI2 Reference switch/
Touch probe sensor
LOW No response
HIGH Activation of reference switch/touch probe sensor (both edge
active)
X6/DI3 Positive hardware limit
switch
LOW The controller reports the activation of the positive hardware
limit switch to the control. A further safety measure can be
implemented by wiring the emergency−off circuit.
HIGH No response
X6/DI4 Negative hardware limit
switch
LOW The controller reports the activation of the negative
hardware limit switch to the control. A further safety
measure can be implemented by wiring the emergency−off
circuit.
HIGH No response

Table of Contents

Other manuals for Lenze ECSEM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECSEM Series and is the answer not in the manual?

Lenze ECSEM Series Specifications

General IconGeneral
BrandLenze
ModelECSEM Series
CategoryControl Unit
LanguageEnglish

Related product manuals