Configuration
Configuring MotionBus/system bus (CAN)
Executing a reset node
8
206
EDBCSXM064 EN 11.0
8.1.5 Executing a reset node
The following changes will only be valid after a reset node:
ƒ Changes of the CAN node addresses and baud rates ( 197)
ƒ Changes of the addresses of process data objects (COB−IDs)
General addressing (
351)
Individual addressing (
201)
ƒ Change of the master/slave boot−up configuration ( 203)
A reset node can be made by:
ƒ Renewed switch−on of the 24 V low−voltage supply
ƒ the bus system (via the network management (NMT))
ƒ C0358/C2458 = 1
Note!
If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0358 Reset node 0
Make a reset node for the CAN
bus node.
206
0 No function
1 CAN reset

Table of Contents

Other manuals for Lenze ECSEM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECSEM Series and is the answer not in the manual?

Lenze ECSEM Series Specifications

General IconGeneral
BrandLenze
ModelECSEM Series
CategoryControl Unit
LanguageEnglish

Related product manuals