Commissioning
Parameter setting with the XT EMZ9371BC keypad
Commissioning example in vector control mode
6
6.3
6.3.2
6.3-6
EDSVF9333V EN 3.0-06/2005
NoteSwitch-on sequence
z Rated motor current (C0088)
Lenze setting: device-dependent
Entervaluefortheselectedmotor
connection method (star/delta)!
z Rated motor frequency (C0089)
Lenze setting: device-dependent
z Rated motor voltage (C0090)
Lenze setting: device-dependent
Entervaluefortheselectedmotor
connection method (star/delta)!
z Motor cosϕ (C0091)
Lenze setting: device-dependent
11. For protecting the motor, set the current limit
values ”I
max
current” (C0022, C0023)
Guide value 2-fold rated motor current
Power range 0.37 ... 90 kW:
For dissipating the regenerative energy,
use a brake chopper or feedback
module, if necessary
Power range 110 ... 400 kW:
For dissipating regenerative energy, use
a brake resistor, if necessary
(see chapter ”Commissioning”
”Motor adjustment” ”Current limit
values”)
A In motor mode and generator mode (C0022)
B Additional limitation in generator mode (C0023)
Condition: C0023 < C0022
12. If the motor temperature is monitored with a
thermal sensor KTY:
Activate the temperature feedback with C0594
(fault SD6)
Lenze setting: 3 (switched off)
A temperature feedback with KTY has a
positive effect on the vector control,
since the motor data identification
considers the temperature influence in
the motor model.
(see chapter ”Commissioning”
”Motor adjustment”)
13. Start the motor data identification ”ident run”
(C0148)
(see chapter ”Commissioning”
”Adjusting the motor”)
A Ensure that the controller inhibit is active
misc008
59 28
X5
}
TerminalX5/28=LOW
B Switch on the mains
C Set C0148 = 1
D Enable controller
misc009
59 28
X5
}
Terminal X5/28 = HIGH
The identification starts:
z The segment goes off
z ”WRK run” is displayed
z The motor is energised and
”whistles”
z The motor does not rotate
E If after approx. 1 ... 2 min the segment is active
again, inhibit the controller
misc008
59 28
X5
}
TerminalX5/28=LOW
The identification is completed. The
following values have been detected
and entered into the codes:
z Inverter error characteristic
(C1753/xx)
z Rotor resistance ”Mot Rr” (C0082)
z Stator resistance ”Mot Rs” (C0084)
z Leakage inductance ”Mot Lss”
(C0085)
z Stator inductance ”Mot Ls” (C0092)
14. Set the operating mode ”vector ctrl” (C0006)
Lenze setting: 5 (V/f characteristic control)
(see chapter ”Commissioning”
”Operating mode” ”Vector control”)
15. Set the switching frequency ”fchop” (C0018)
Lenze setting:
Power range 0.37 ... 90 kW: 6 (8/2 kHz sin)
Power range 110 ... 400 kW: 6 (4/2 kHz sin)
See chapter ”Commissioning”
”Switching frequency of the inverter”
16. Set your type of t he speed feedback system
”Feedback type” (C0025)
Lenze setting: 1 (no f eedback)
See chapter ”Commissioning”
”Setting of speed feedback”
A When using a TTL encoder:
Select the encoder used under C0025