Troubleshooting and fault elimination
Error elimination
Error messages at the keypad or in the parameter setting program Global Drive Control
9
9.4
9.4.4
9.4-9
EDSVF9333V EN 3.0-06/2005
RemedyCauseFaultError number
x=0:TRIP
x = 1: Message
x=2:Warning
Error
code
PR0 x075 Parameter set error Error while loading a parameter set. The
parameters saved are not suitable for
the software version of the controller.
Caution! The Lenze setting is loaded
automatically.
z Correct parameter set
z Save all parameter sets with C0003
and reset the fault message by mains
switching
PR1
PR2
PR3
PR4
x072
x073
x077
x078
Parameter set error z Fault while loading a parameter set
z The transmission of parameter sets
with keypad XT has been interrupted
(e.g. by an early disconnection of the
keypad XT)
Caution! The Lenze setting is loaded
automatically.
Set the required parameters and save
them with C0003
Sd3 x083 EncodererroratX9
Cable interrupted Check cable for wire breakage
Pin X9/8 is not assigned AssignpinX9/8with5Vorswitchoff
monitoring (C0587 = 3)
Sd5 x085 Encoder at X6/1,
X6/2 is defect
CurrentatX6/1,X6/2<2mA z Check cable for wire breakage
z Check encoder
Sd6 x086 Sensor error at X8 KTY at X8 indicates undefined values z Check supply cable for firm
connection
z Switch off monitoring with C0594 = 3
if necessary