IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0912 OV delay time Æ - {1 ms} - Delay time of the pulse release
after an OU message
Æ depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0912 to the time of the
selected motor
z Thetimeisderivedfromthe
double rotor time constant
8.2-25
8.2-48
9.4-3
C0913
OV handling 0 Value of the motor current during
the flying restart process or after
an OU message
z When C0913 = 1, the motor is
driven with reduced current to
the setpoint speed during the
flying restart process of after an
OU message.
z The setting is only effective for
the drives EVF9326 ... EVF9333
8.2-25
8.2-48
0 inactive Non-reduced motor current
1 active Reduced motor current
ƒ The signal at input MCTRL-N-SET is the speed setpoint in [%] and
always refers to the maximum speed (C0011).
ƒ In the most basic configurations, MCTRL-N-SET is connected with the
function block NSET (speed setpoint conditioning).
– It is also possible to connect MCTRL-N-SET with any other analog
output signal of an FB.
ƒ The speed setpoint at MCTRL-N-SET is always limited to ±100 % of the
maximum speed n
max
(C0011).
ƒ The speed setpoint is converted into a frequency setpoint by the motor
control and limited to a maximum output frequency depending on the
chopper frequency f
chop
.
Chopper frequency f
chop
Maximum output frequency
16 kHz 600Hz
8kHz 300Hz
2/4 kHz 150Hz
Speed setpoint selection
Speed setpoint limitation