Configuration
Code table
8
8.3
8.3-66
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C1320
CFG: SET 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block DCALC1
z Setting the initial value
8.2-1
C1321
Selection list 2 Configuration of digital input
signals, function block DCALC1
1 CFG: LOAD 1000 FIXED0 z HIGH: Initial value at
DCALC1-SET is accepted
z DCALC1-LOAD has a higher
priority than DCALC1-HOLD
2 CFG: HOLD 1000 FIXED0 z HIGH = Keeps the achieved
diameter and resets the
integrators.
C1322 -36000 {1 rpm} 36000
Function block DCALC1
z Display of the signals linked in
C1327
8.2-1
1 DIS: N-Line
2 DIS: N-WIND
C1325 DIS: SET -199.99 {0.01 %} 199.99 Function block DCALC1
z Display of the signal linked in
C1320
C1326 0 1
Function block DCALC1
z Display of the signals linked in
C1321
1 DIS: LOAD
2 DIS: HOLD
C1327
Selection list 3 Configuration of input signals,
function block DCALC1
8.2-1
1 CFG: N-Line 1000 FIXED0INC z Speed signal of the line drive
2 CFG: N-WIND 1000 FIXED0INC z Speed signal of the winding
drive
C1328 DIS: D-ACT -200 {1 mm} 200 Function block DCALC1
z Display of the current
diameter
C1330 PCTRL2 Tir 1.0 0.1 {0.1 s 6000.0 Acceleration time t
ir
, function
block PCTRL2
z Acceleration time for the
setpoint
z The acceleration time refers to
a setpoint change of 0 ... 100 %
See System
Manual
(extension)
C1331 PCTRL2 Tif 1.0 0.1 {0.1 s} 6000.0 Deceleration time t
if
, function
block PCTRL2
z Deceleration time for the
setpoint
z The deceleration time refers to
a setpoint change of 100 % ... 0
C1332 PCTRL2 Vp 1.0 0.1 {0.1 } 500.0 Gain V
p
, function block PCTRL2
See System
Manual
(extension)
C1333 PCTRL2 Tn 400 20 {1 ms} 99999 Integral-action time T
n
, function
block PCTRL2
Setting of reset time T
n
of PCTRL2
C1334 PCTRL2 Kd 0.0 0.0 {0.1 } 5.0 Differential component K
d
,
function block PCTRL2
C1335 bipolar/unipolar 0
Sphere of action, function block
PCTRL2
0 Bipolar z Output value is limited to
-100 ... 100 %
See System
Manual
(extension)
1 Unipolar z Output value is limited to
0 ... 100 %