Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8
8.2
8.2.7
8.2-52
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0084
Mot Rs Æ 0.00 {0.01 mΩ} 100000.
00
Motor stator resistance
Æ Value is determined by motor
parameter identification
(C0148, C0149)
6.6-1
6.6-13
C0085
Mot Lss Æ 0.0 {0.1 mH} 6500.0 Motor leakage inductance
Æ Value is evaluated by motor
parameter identification
(C0148, C0149)
6.6-1
6.6-13
C0086
Mot type Æ Motor selection list Motor type selection
Æ depending on the controller
used
z Motor selection in C0086 sets
the corresponding parameters
in C0021, C0022, C0081, C0087,
C0088, C0089, C0090, C0091
6.6-1
C0087
Mot speed Æ 50 {1 rpm} 36000 Rated motor speed
Æ depending on C0086
z Motor selection in C0086 set
the corresponding rated motor
speed in C0087
z Change of C0087 sets
C0086 = 0
6.6-1
C0088
MOT CURRENT Æ 0.5 {0.1 A} 500.0 Rated motor current
Æ Depending on C0086
z Selection of a motor in C0086
sets the corresponding rated
motor current in C0088
z Change of C0088 sets
C0086 = 0
6.6-1
C0089
Mot frequency Æ 10 {1 Hz} 5000 Rated motor frequency
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding rated motor
frequency in C0089
z Change of C0089 sets
C0086 = 0
6.6-1
C0090
Mot voltage Æ 0 {1 V} 1000 Rated motor voltage
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090
z Change of C0090 sets C0086 =
0
6.6-1
C0091
Mot cos phi Æ 0.50 {0.01 } 1.00 Motor cos ϕ
Æ depending on C0086
z Motor selection in C0086 sets
the corresponding motor cos ϕ
in C0091
z Change of C0091 sets
C0086 = 0
6.6-1
C0092
Mot Ls Æ 0.0 {0.1 mH} 6500.0 Motor stator inductance
Æ Value is evaluated by motor
parameter identification from
C0088, C0089, C0090 and
C0091
Æ Selection of a motor in C0086
sets the corresponding stator
inductance value in C0092
6.6-1