Page #154 background image
Commissioning
Changing the assignment of the control terminals X5 and X6
Free configuration of digital input signals
6
6.5
6.5.1
6.5-1
EDSVF9333V EN 3.0-06/2005
6.5 Changing the assignment of the control terminals X5 and X6
Danger!
If you select a configuration in C0005, the signal assignment of
the inputs and outputs will be overwritten with the
corresponding basic assignment!
ƒ Adapt the signal assignment to your wiring!
6.5.1 Free configuration of digital input signals
ƒ Internal digital signals can be freely linked with external digital signal
sources. It serves to establish a freely configurable control of the drive
controller.
Digital inputs X5/E1 ... X5/E5
ƒ A signal source can be linked with several targets. Ensure reasonable
linkages for not activating functions that are mutually exclusive (e. g.
linking a digital input with quick stop and DC injection braking at the
same time).
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0114
0 High active HIGH level is
active
Inversion of digital input signals at
X5, function block DIGIN
6.5-1
See System
Manual
(extension)
1 LOW active LOW level is active
1 DIGIN1 pol 0 Terminal X5/E1
2 DIGIN2 pol 0 Terminal X5/E2
3 DIGIN3 pol 0 Terminal X5/E3
4 DIGIN4 pol 1 Terminal X5/E4
5 DIGIN5 pol 0 Terminal X5/E5
5 DIGIN6 (ST) pol 0 Terminal X5/ST
Description