Technical data
Fuses and cable cross-sections
DC supply
3
3.5
3.5.2
3.5-5
EDSVF9333V EN 3.0-06/2005
3.5.2 DC supply
Stop!
ƒ Only use semiconductor fuses.
ƒ On principle, fuse DC cables as 2-pole (+U
G
,-U
G
).
9300 vector DCfuse14×51
(EFSGR0xx0AYHx)
DCfuse22×58
(EFSGR0xx0AYIx)
Installation to
EN 60204-1
1)
Installation
to UL
Type Fused rated current
2)
Fused rated current
2)
+U
G
,-U
G
Laying system
+U
G
,-U
G
B2 C
[A] [A] [mm
2
] [mm
2
] [AWG]
EVF9321 10 12 1.5 1.5 16
EVF9322 10 12 1.5 1.5 16
EVF9323 10 12 1.5 1.5 16
EVF9324 20 20 4 2.5 12
EVF9325 32 32 10 6 8
EVF9326 40 40 10 10 8
EVF9327 80 35 25 1
EVF9328 100 35 1
EVF9329 2×80 2×25 2×3
EVF9330 2 × 100 2×35 2×1
EVF9331 3×80 3×25 3×3
EVF9332 3 × 100 3×35 3×1
EVF9333 4 × 100 4×35 4×1
1)
The specifications are recommendations. Other designs/laying systems are possible.
The cable cross-sections apply under the following conditions: Use of PVC-insulated copper leads,
conductor temperature < 70 °C, ambient temperature < 40 °C, no bundling of cables or cores
2)
The rated currents of the fuses EFSGR0xx0AYHx and EFSGR0xx0AYIx of Lenze are given. When
using other fuses, other fuse currents and cable cross-sections may arise.
National and regional regulations must be observed