Features of ”maximum output frequency” (n
max
):
ƒ When selecting fixed setpoints (JOG), C0011 acts as limitation.
ƒ C0011 is an internal scaling variable! Therefore m ajor changes may
only be carried out when the controller is inhibited!
Stop!
Set 0011 so that the maximum permissible motor speed is not
exceeded.
Otherwise the motor will be destroyed.
The internal speed limits must be observed (p = number of motor pole pairs):
ƒ Switching frequency 16 kHz: n
max
= 36000/p min
-1
ƒ Switching frequency 8 kHz: n
max
= 36000/2p min
-1
ƒ Switching frequency 2/4 kHz: n
max
= 36000/4p min
-1
C0011
Setting tips