5.26.- NO. OF OPERATIONS ALARM
In this point the number of operations of any of the
stages above which the alarm E17 will be triggered
can be configured.
The alarms must be enabled ( 5.19.- ENABLING
ALARMS”)
Press the key to enter editing mode. It is
identified by the symbol and the blinking of
the digits to be modified.
There are thousands of operations (k), so a value of 100 k will mean 100,000 operations.
The key increases the digit value.
The key decreases the digit value.
The key skips to the previous digit.
The key skips to the next digit.
Press to validate the data; the symbol disappears from the display.
Maximum value: 99999 k.
Minimum value: 1 k.
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display ashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen, 5.27.-
SIMULATION SCREEN.
101
Instruction Manual
Controller MASTER control VAR FAST

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lifasa MASTER control Var and is the answer not in the manual?

Lifasa MASTER control Var Specifications

General IconGeneral
BrandLifasa
ModelMASTER control Var
CategoryController
LanguageEnglish

Related product manuals