5.4.- CONNECTION AND RECONNECTION TIME
In this point the action times of the device are
configured in seconds:
Ton is the minimum time between the connection
and disconnection of a single stage (counted in
number of network cycles).
TREC is the minimum time between the
disconnection and connection of a single stage
(counted in number of network cycles).
Press the key to enter editing mode. It is identified by the symbol and the blinking
of the digits to be modified.
The key increases the digit value.
The key decreases the digit value.
The key skips to the previous digit.
The key skips to the next digit.
Press to validate the data; the symbol disappears from the display.
Ton:
Maximum value: 999.
Minimum value: 2.
Trec:
Maximum value: 999.
Minimum value: 0.
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display ashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the key to access the next programming step
If no keys are pressed for 5 minutes, the unit switches to the simulation screen, 5.27.-
SIMULATION SCREEN.
77
Instruction Manual
Controller MASTER control VAR FAST

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lifasa MASTER control Var and is the answer not in the manual?

Lifasa MASTER control Var Specifications

General IconGeneral
BrandLifasa
ModelMASTER control Var
CategoryController
LanguageEnglish

Related product manuals