EasyManuals Logo
Home>Lifasa>Controller>MASTER control Var

Lifasa MASTER control Var User Manual

Lifasa MASTER control Var
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
Press the key to enter editing mode. It is
identified by the symbol and the blinking of
the digits to be modified.
The key increases the digit value.
The key decreases the digit value.
The key skips to the previous digit.
The key skips to the next digit.
Press to validate the data; the symbol disappears from the display.
Minimum value: 0.02
Maximum value: 1.0
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display ashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen, 5.27.-
SIMULATION SCREEN.
5.10.- ADVANCED SETUP
In this point it is possible to decide whether to
access the advanced setup menu.
If the YES option is selected, the next programming
step will be the voltage transformation ratio ("5.11.-
VOLTAGE TRANSFORMATION RATIO)
When the No option is selected, the display returns
to the Plug&Play configuration screen ("5.1.-
PLUG&PLAY”)
Press the key to enter editing mode. It is identified by the symbol and the blinking
of the digits to be modified.
The key shows the next option.
84
Controller MASTER control VAR FAST
Instruction Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lifasa MASTER control Var and is the answer not in the manual?

Lifasa MASTER control Var Specifications

General IconGeneral
BrandLifasa
ModelMASTER control Var
CategoryController
LanguageEnglish

Related product manuals