5.15.- FAN
In this point the activation of the relay output
associated with the fan can be configured.
It is possible to configure whether it is enabled
ON or not OFF, as well as the temperature above
which it is to be activated or deactivated.
The unit has a hysteresis value of 5ºC when
disconnecting the fan, in order to avoid continuous
connections and disconnections.
Press the key to enter editing mode. It is identified by the symbol and the blinking
of the digits to be modified.
The key increases the digit value or shows the next option.
The key decreases the digit value or shows the next option.
The key skips to the previous parameter.
The key skips to the next parameter.
Press to validate the data; the symbol disappears from the display.
Maximum value: 80ºC.
Minimum value: 0ºC.
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display ashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen, 5.27.-
SIMULATION SCREEN.
89
Instruction Manual
Controller MASTER control VAR FAST

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lifasa MASTER control Var and is the answer not in the manual?

Lifasa MASTER control Var Specifications

General IconGeneral
BrandLifasa
ModelMASTER control Var
CategoryController
LanguageEnglish

Related product manuals