14 NIBE F1330
Installation / Adjustment
Docking
Docking
General
F1330 can be installed in several different ways, some of
which are described below.
More docking options can be found at
http://www.nibe.eu
F1330 gives priority to hot water charging at half power
(heat pump module B) via a shuttle valve (RV). When the
water heater/accumulator tank (VVB/ACK) is fully charged
the shuttle valve (VXV) switches over to the heating circuit.
When there is a heat requirement, module A starts first.
For larger requirements, module B takes care of the heat-
ing. The boiler is connected automatically when the en-
ergy demand exceeds the capacity of the heat pump and
the shunt (SV-P) is activated when the temperature on the
boiler sensor (PG) is above 55 °C.
If VVB/ACK is fitted with an immersion heater (IU) and a
junction box (K11) the Extra hot water function can be
used. A by-pass contactor is recommended.
Example F1330 docked with an oil boiler/pellet boiler and water heater (floating condensing)
The safety equipment must be installed in
accordance with current regulations for all
docking options.
NOTE!
FG Flow sensor
HR Auxiliary relay /Contactor with by-pass
KB-in Brine in
KB-ut Brine out
PG Boiler sensor
RG Return sensor
RV Control valve
SF Particle filter
SV-P Shunt
SÄV Safety valve
UG Outside temperature sensor
VBP3 Heating medium pump 3
VVB Water heater
VVB/ACK Accumulator with water heater
VVG Hot water sensor
VXV Shuttle valve
A Heat pump module A
AV Shutoff valve
B Heat pump module B
BV Non-return valve
EXP Expansion tank with necessary safety equipment
* Dotted safety valve – must be used in connection with
immersion heater.
** The brine pump for 60 kW is supplied and installed
externally outside the heat pump.
Panna
UG
PG
PG
SV-P
SV-P
VVB / AC K
HR
EXP
EXP
SÄV
SÄV
EXP
SÄV
CP
AV
AV
SÄV
VXV
BV
BV
BVRV
RV
RV
RG
FG
VVB
HR
SF
SF
VBP3
HR
SÄV*
Elkassett/
Elpanna
Fjärrvärmeväxlare
B
A
Oljepanna alternativt elpanna
med shunt
Fjärrvärme
Mindre elpanna med flera elsteg
Tillsatsvärme
T
Master
VP1
AV
AV
SÄV
SF
P
EXP
AV
KB-ut
KB-in
AV
**
Oil-fired boiler or electric boiler
with shunt
Smaller electric boiler
with several electrical steps
Immersion heater /
Electric boiler
District heating
Remote heat exchanger
Additional heat