4.0 Outdoor temperature
Menu 4.1 Medium outdoor temp. [N]
The average outdoor temperature for the last 24 hours is
shown here.
Menu 4.2 Return [N]
Pressing the Enter button returns you to menu 4.0.
5.0 Heat pump
Menu 5.1 Heat pump unit [N]
The heat pump unit is selected here, for which submenus
to menu 5.0 applies:
Master / Slave 1 / Slave 2 / ... / Slave 8.
Only activated units can be selected (menu 0.2).
Menu 5.2.0 Compressor module A [N]
The current mode of compressor module A is shown here:
”Heat / Hot water / Ext. control / Waiting / Alarm / Off”.
Pressing the enter button takes you to the sub-menus that
show the temperatures and statistics for compressor mod-
ule A.
Menu 5.2.1 Heating flow/return [N]
The internal flow (VBFA) and return temperatures (VBRA)
are shown here for the heat medium to the compressor
module A.
Menu 5.2.2 Brine in/out [N]
The current incoming (KBinA) and outgoing temperature
(KButA) are shown here for brine to the compressor mod-
ule A.
Menu 5.2.3 Hot gas temperature [U]
The current hot gas temperature for compressor module A
at the sensor (HGA) is shown here.
Menu 5.2.4 Overheating temp. [U]
The current bulb temperature for compressor module A at
the sensor (BA) is shown here.
Menu 5.2.5 Liquide line temp. [U]
The current fluid line temperature for compressor module
A at the sensor (VLA) is shown here.
Menu 5.2.6 Tot. starts compr. A [U]
The number of times that compressor A has been started
since the first start up is shown here. The value is saved in
the microprocessor and thus is not reset even when the
heat pump is switched off using the main power switch.
Menu 5.2.7 Opera.time compr. A [U]
The number of hours that compressor A has been in op-
eration since the first start up is shown here. The value
is saved in the microprocessor and thus is not reset even
when the heat pump is switched off using the main power
switch.
Menu 5.2.8 Return [N]
Pressing the enter button returns you to menu 5.2.0.
Menu 5.3.0 Compressor module B [N]
The current mode of compressor module B is shown here:
”Heat / Hot water / Ext. control / Waiting / Alarm / Off”.
Pressing the enter button takes you to the sub-menus that
show the temperatures and statistics for compressor mod-
ule B.
Menu 5.3.1 Heating flow/return [N]
The internal flow (VBFB) and return temperatures (VBRB)
are shown here for the heat medium to the compressor
module B.
Menu 5.3.2 Brine in/out [N]
The current incoming (KBinB) and outgoing temperature
(KButB) are shown here for brine to the compressor mod-
ule B.
Menu 5.3.3 Hot gas temperature [U]
The current hot gas temperature for compressor module B
at the sensor (HGB) is shown here.
Menu 5.3.4 Overheating temp. [U]
The current bulb temperature for compressor module B at
the sensor (BB) is shown here.
Menu 5.3.5 Liquide line temp. [U]
The current fluid line temperature for compressor module B
at the sensor (VLB) is shown here.
Menu 5.3.6 Tot. starts compr. B [U]
The number of times that compressor B has been started
since the first start up is shown here. The value is saved in
the microprocessor and thus is not reset even when the
heat pump is switched off using the main power switch.
Menu 5.3.7 Opera.time compr. B [U]
The number of hours that compressor B has been in op-
eration since the first start up is shown here. The value
is saved in the microprocessor and thus is not reset even
when the heat pump is switched off using the main power
switch.
Menu 5.3.8 Return [N]
Pressing the enter button returns you to menu 5.3.0.
Menu 5.4.0 Settings [U]
Pressing the enter button takes you to the settings for the
unit selected in menu 5.1.
Menu 5.4.1 Max.heat returntemp. [U]
The maximum permitted heating medium-return tempera-
ture for the compressor is displayed here.
Menu 5.4.2 Min. brine out [U]
The minimum permitted brine temperature out from the
heat pump. Can be set between -10 and +15 °C or Off.
The factory setting is -8 °C.
Menu 5.4.3 Max. brine in [U]
Maximum permitted brine temperature in to the heat
pump. Can be set between -10 and +40 °C or Off. The
factory setting is Off.