61NIBE F1330
Control
6.0 External units*
* Only shown when the accessory in question is connected and
activated in menu 9.1.x.
Menu 6.1.0 Circulation pumps [U]
Pressing the enter button takes you to the sub-menus for
the circulation pumps. Settings are made here for internal
and external circulation pumps.
Menu 6.1.1 Op-mode external cp [U]
The operating mode for an external heating medium pump
(VBP3) is set here. Selectable options are:
Continuous: Continuous operation.
Economy: The pump is operational a specific time per
period (see menu 6.1.2 and 6.1.3), and together with the
compressor.
The factory setting is Continuous.
Menu 6.1.2 Periodtime economy [U]
Here the period time for economy mode is set here. This
applies to heating medium pump A/B (VBP-A/VBP-B) when
Economy is selected in menu 5.4.7/5.4.8, and/or the exter-
nal heating medium pump (VBP3) when Economy is select-
ed in menu 6.1.1. Adjustable between 5 and 120 minutes.
The factory setting is 20 minutes.
Menu 6.1.3 Operati-time econom [U]
The operating time per period for the economy mode
is selected here. This applies to heating medium pump
A/B (VBP-A/VBP-B) when Economy is selected in menu
5.4.7/5.4.8, and/or the external heating medium pump
(VBP3) when Economy is selected in menu 6.1.1.
Adjustable between 1 and 120 minutes.
The factory setting is 5 minutes.
Menu 6.1.4 Time of period Hw-cp [U]
Here you select between which times of the day the hot
water circulation pump shall run according to the period
time (menu 6.1.5) and the operating time (menu 6.1.6).
Menu 6.1.5 Periodtime Hw-cp [U]
Here the period time for the hot water circulation pump is
set here. Adjustable between 10 and 60 minutes. The fac-
tory setting is 15 minutes.
Menu 6.1.6 Operatingtime Hw-cp [U]
The operating time per period for the hot water circulation
pump is selected here. Adjustable between 1 and 60 min-
utes. The factory setting is 3 minutes.
Menu 6.1.7 Return [U]
Pressing the enter button returns you to menu 6.1.0.
Menu 6.2.0 Immersionheatersetti [N]
The number of electrical steps activated is shown with the
text, x el. steps. Pressing the enter button takes you to sub-
menus where settings concerning the connected electri-
cal additional heater for heat production are made. Only
shown when Electricity or Electri/Oil is selected in menu
9.1.8.
Menu 6.2.1 Immersionheater type [U]
Here you select whether immersion heater control shall
take place in binary or linear.
Binary control means that stepping is carried out according
to the binary system and in doing so makes it possible to
control a maximum of 63 electrical steps.
Linear control gives a maximum of 6 electrical steps when
stepping is carried out according to the linear increase
model.
Menu 6.2.2 Immersionheatrelays [U]
Here you select how many relays are connected to the
electrical additional heater for heat production. Adjustable
between 1 and 6. The factory setting is 3.
Menu 6.2.3 Steps at 2h delay [U]
The number of permitted electrical steps within 2 hours of
start up. Adjustable between 0 and 63. The factory setting
is 3.
Menu 6.2.4 Quickstart el.heater [U]
Select Yes to bypass the 2-hour electrical additional heater
delay
NOTE! The setting returns to No as soon as the heat pump
has implemented the action.
Menu 6.2.5 Time factor el.cass. [U]
The time factor of the immersion heater since first start up
is shown here. The value is saved in the microprocessor and
thus is not reset even when the heat pump is switched off
using the main power switch.
Menu 6.2.6 Return [U]
Pressing the enter button returns you to menu 6.2.0.
Menu 6.3.0 Boiler settings [N]
Shows the temperature level of the oil boiler. Pressing the
enter button takes you to sub-menus for the boiler set-
tings. Only shown when Oil or Electri/Oil is selected in
menu 9.1.8.
Menu 6.3.1 Oil boiler time [U]
Number of hours the oil boiler shall be active. The value
can be set between 1 and 24 hours. The factory setting is
12 hours.
Menu 6.3.2 Start temp. shunt [U]
Here you select the temperature on the boiler sensor (PG)
at which the boiler shunt (SV-P) should start to regulate.
Adjustable between 10 and 90 °C. The factory setting is
55 °C.
Menu 6.3.3 Period time shunt [U]
Here you select the period time, i. e. the time between
corrections for the shunt (SV-P). Adjustable between 10
and 500 seconds. The factory setting is 120 seconds.