56 NIBE F1330
Control
Control
0.0 System
Menu 0.1.0 Status [N]
The number of compressor modules that produce hot
water (HW), radiator heating (Rad), pool heating (Pool) or
cooling (Cold) are shown here.
Menu 0.1.1 Status Master A [N]
The current mode of compressor module A is shown here:
Heat / Hot water / Ext. control / Wait xx min / Alarm
Menu 0.1.2 Status Master B [N]
The current mode of compressor module B is shown here:
Heat / Hot water / Ext. control / Wait xx min / Alarm
Menu 0.1.3 – 0.1.18 Status Slave 1A – Slave 8B* [N]
The current mode of for compressor modules A or B in
every Slave is shown here:
Heat / Hot water / Ext. control / Waiting / Alarm
Menu 0.1.19 Return [N]
Pressing the Enter button returns you to menu 0.1.0
Menu 0.2.0 Oper.type setting [S]
Pressing the enter button takes you to the sub-menus
where the heat pump’s operating type is selected, options
are:
Off: Compressor modules A and B are not used.
Heat: Compressor modules A and B only provide heating.
Hot water: Compressor modules A and B only provide
hot water.
Combi: Compressor module B provides both hot water
and heating via the shuttle valve, while compressor mod-
ule A always provides heating.
Parallel: Compressor modules A and B provide both hot
water and heating via the shuttle valve.
External control: Start and stopsignal from external
equipment.
Menu 0.2.1 Oper.type Master [S]
The operating type for the Master is selected here. The
factory setting is Off.
Menu 0.2.2 – 0.2.9 Oper.type Slave 1 – 8 [S]
The operating type for the slave/slaves is selected here.
The factory setting is Off.
Menu 0.2.10 Return [S]
Pressing the enter button returns you to menu 0.2.0.
Menu 0.3 Return [N]
Pressing the enter button returns you to menu 0.0.
* Slaves 1-8 are only shown when activated in menu 0.2.2 - 0.2.9.
1.0 Hotwater temperature
Menu 1.1 Start temperature HW [U]
The temperature when the heat pump starts to work with
the hot water production is set here. When brackets are
shown, this means the high pressure pressostat has tripped
during hot water charging and F1330 has automatically
lowered the set temperature with the value in brackets.
The reduction is removed when the value is manually
changed. The value is adjustable between 5 and 55 °C. The
factory setting is 45 °C.
Menu 1.2 Stop temperature HW [U]
The temperature when the heat pump stops working with
the hot water production is set here. When brackets are
shown, this means the high pressure pressostat has tripped
during hot water charging and F1330 has automatically
lowered the set temperature with the value in brackets.
The reduction is removed when the value is manually
changed. The value is adjustable between 20 and 60 °C.
The factory setting is 50 °C.
Menu 1.3 Stop temp. compr XHW [U]
Here the temperature at which the compressor shall stop
producing hot water in Extra hot water and allow the addi-
tional heat (XVV) to take over is set. The value is adjustable
between 20 and 60 °C, or Off. The factory setting is 50 °C.
Menu 1.4 Stop temperature XHW [U]
The required temperature for Extra hot water, when the
additional heat shall stop during hot water production is
set here. The value is adjustable between 50 and 80 °C, or
Off. The factory setting is Off.
Menu 1.5 Interval per. XHW [U]
How often the hot water temperature is increased from
the normal level to the “Extra hot water” level is shown
here. Periodic “Extra hot water” is activated when the value
changes. The digit within brackets indicates the time in days
that remain until the next periodic “Extra hot water” in-
crease. When periodic hot water heating runs, the number
between brackets changes to show the number of minutes
that remain before it is ready. The value is adjustable be-
tween 1 and 90 days, or “Off”. The factory setting is “Off”.
Menu 1.6 Periodtime HW/Heat. [U]
The length of the period time for hot water production and
heating is set here. The value is adjustable between 5 and
60 minutes. The factory setting is 60 minutes.
Menu 1.7 Maxtime HW-product. [U]
Here you select how much time of the period time
(menu
1.6)
is to be used to heat the hot water when there is a need
of both heating and hot water. The value is adjustable be-
tween 0 and 60 minutes. The factory setting is 60 minutes.
Menu 1.8 Diff between compr. [U]
The difference between connection and disconnection of
compressors during hot water charging and fixed condens-
ing if several are available for hot water charging. The value
is adjustable between 0 and 10 °C. The factory setting is 0.5 °C.