3.13 Prevent Switching Surge
106 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
3.13 Prevent Switching Surge
Connect a Surge Protective Device
A surge protective device decreases the surge voltage that is generated from switching an inductive load near the
drive. Inductive loads include:
Magnetic contactors
Electromagnetic relays
Magnetic valves
Solenoids
Magnetic brakes.
Always use a surge protective device or diode with inductive loads.
Note:
Do not connect a surge protective device to the drive output side.