Inverter Specifications
A–12 976-0043-01-02
Inverter Capacity versus Temperature
The output power of the inverter diminishes as ambient temperature rises.
However, as can be seen below, with the exception of the SWP5548, these
inverters are sized to be able to run a full rated output power up to 40C.
However, it should be noted that the overcurrent circuit on the unit is
temperature compensated to protect the unit and that the thermal circuit
breaker will trip at a lower current as the temperature rises. Therefore, the
surge ability of the unit decreases with increased temperature.
This table refers to output VA only. Testing was conducted in a thermal
chamber with the inverters as stand-alone units without accessories.
Table A-1
Derating from continuous power (VA) at elevated ambient
temperatures
Model 25° C 30 ° C 35° C 40° C
SW Plus 2524 No Derating No Derating No Derating No Derating
SW Plus 2548 No Derating No Derating No Derating No Derating
SW Plus 4024 No Derating No Derating No Derating No Derating
SW Plus 4048 No Derating No Derating No Derating No Derating
SW Plus 5548 No Derating No Derating No Derating 5.3KVA