Multi-wire Branch Circuits
976-0043-01-02 F–3
Figure F-2
Multi-wire Branch Circuit Wiring and Current Flow
Figure F-3
120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit
Load Center
L1
L2
Neutral
Ground
120 Vac
120 Vac
15 A
Breaker
(Ganged)
2
40 Vac
fr
om Grid
Bare - Ground
Single White - Neutral
(Current Flow 0 A)
Black - Hot
(Current Flow 15 A)
Red - Hot
(Current Flow 15 A)
Bare - Ground Splice
White - Neutral Splice
(Current Flow 15 A)
Out-of-Phase current
subtract at this point
(Current Flow 0 A)
15 A
Breaker
(Ganged)
Load Center
L1
L2
Neutral
Ground
120 Vac 120 Vac
15 A
Breaker
(Ganged)
240 Vac
from Grid
Bare - Ground
Single White - Neutral
(Current Flow 10 A)
Black - Hot
(Current Flow 5 A)
Red - Hot
(Current Flow 15 A
)
White - Neutral Splice
(Current Flow 15 A)
When unbalanced
current flows through
each leg, only the
difference current
flows through the
neutral return wire.
15 A
Breaker
(Ganged)
Load Center
L1
L2
Neutral
Ground
120 Vac 120 Vac
15 A
Breaker
(Ganged)
Bare - Ground
Single White - Neutral
(Current Flow 30 A)
Black - Hot
(Current Flow 15 A)
Red - Hot
(Current Flow 15
A
White - Neutral Splice
(Current Flow 15 A)
WARNING: FIRE HAZARD
The in-phase currents ADDS
at this point exceeding wire
capacity!
15 A
Breaker
(Ganged)
120 Vac
Inverter or Generator

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex SW Plus 2524 and is the answer not in the manual?

Xantrex SW Plus 2524 Specifications

General IconGeneral
BrandXantrex
ModelSW Plus 2524
CategoryInverter
LanguageEnglish

Related product manuals