6-86
Setting Precautions
To switch command inputs between the Communications Option Board and the control circuit terminals, set
the following constants.
• Set b1-01 (Reference Selection) to 1 (Control circuit terminal [analog input])
• Set b1-02 (Operation Method Selection to 1 (Control circuit terminal (sequence inputs])
• Set one of the constants H1-01 to H1-06 (multi-function contact input terminal S3 to S8 function selection)
to 2 (Option/Inverter selection).
îš‹ Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)
The FJOG/RJOG command functions operate the Inverter using jog frequencies by using the terminal ON/
OFF operation. When using the FJOG/RJOG commands, there is no need to input the Run Command.
To use this function, set one of the constants H1-01 to H1-06 (multi-function contact input terminal S3 to S8
function selection) to 12 (FJOG command) or 13 (RJOG command).
Related Constants
* 1. The upper limit of the setting range depends on the upper limit set in E1-04.
* 2. When C6-01 = 1, the upper limit is 400.00.
* 3. When C6-01 = 0, the upper limit is 150.00.
Multi-Function Contact Inputs (H1-01 to H1-06)
Terminal Status Frequency Reference and Run Command Selection
OFF
Inverter
(Can be operated from frequency reference or control circuit terminal from analog input termi-
nal.)
ON
Communications Option Board
(Frequency reference and Run Command are enabled from Communications Option Board.)
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
d1-17
Jog frequency
reference
The frequency reference when
the jog frequency reference
selection, FJOG command, or
RJOG command is ON.
0.00 to
400.00
*1 *3
6.00 Hz Yes Q Q Q Q 292H
0.00 to
300.00
*1 *2
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals