Section 2 IED engineering process
PCM600 is used for various tasks in the IED engineering process.
IED engineering management
Organizing the bay IEDs in the structure of the substation by defining
voltage levels and bays below the substation. PCM600 manages the project.
Configuring the IED functions (for example, protection and control
functions) by using the Application Configuration tool.
Configuring the parameters and setting values for the IED itself and for the
process functions by using the Parameter Setting tool.
Drawing single-line diagrams and making links to dynamic process values
by using the Graphical Display Editor. The single-line diagrams are
displayed in LHMI on the bay IED.
Configuring connections between the application configuration function
blocks and physical hardware input and outputs by using the Signal Matrix
tool.
Communication management
IEC61850 station communication engineering can be done with the
IEC61850 Configuration tool within PCM600 for small to moderate station
level projects including only Relion products. A separate tool like IET600 is
required for integration with non-Relion products as well as for large
projects. PCM600 interacts with IET600 or any external tool by importing
and exporting SCL files.
Configuring the GOOSE receive data connections to the IED's application
configuration function blocks by using the Application Configuration tool
and the Signal Matrix tool.
Configuring protocol data mapping for Modbus or DNP3 with the
Communication Management tool.
Disturbance record management
1MRS240044-IB A Section 2
IED engineering process
REF615R 13
Engineering Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF615R and is the answer not in the manual?

ABB REF615R Specifications

General IconGeneral
BrandABB
ModelREF615R
CategoryRelays
LanguageEnglish

Related product manuals