Section 2 IED engineering process
PCM600 is used for various tasks in the IED engineering process.
• IED engineering management
• Organizing the bay IEDs in the structure of the substation by defining
voltage levels and bays below the substation. PCM600 manages the project.
• Configuring the IED functions (for example, protection and control
functions) by using the Application Configuration tool.
• Configuring the parameters and setting values for the IED itself and for the
process functions by using the Parameter Setting tool.
• Drawing single-line diagrams and making links to dynamic process values
by using the Graphical Display Editor. The single-line diagrams are
displayed in LHMI on the bay IED.
• Configuring connections between the application configuration function
blocks and physical hardware input and outputs by using the Signal Matrix
tool.
• Communication management
• IEC61850 station communication engineering can be done with the
IEC61850 Configuration tool within PCM600 for small to moderate station
level projects including only Relion products. A separate tool like IET600 is
required for integration with non-Relion products as well as for large
projects. PCM600 interacts with IET600 or any external tool by importing
and exporting SCL files.
• Configuring the GOOSE receive data connections to the IED's application
configuration function blocks by using the Application Configuration tool
and the Signal Matrix tool.
• Configuring protocol data mapping for Modbus or DNP3 with the
Communication Management tool.
• Disturbance record management
1MRS240044-IB A Section 2
IED engineering process
REF615R 13
Engineering Manual