Diagmessages of module AxisMain
Multi axis servo system - AX8000 105
Version: 1.1
6.6 2383, Phase U current offset out of range
The measured current offset of Phase U is outside the accepted range.
Diagnostic Code (Hex.) Diagnostic Code (Dez.)
2383 9091
Class Type
Error Error
Standard Reaction Reset
Torque off Execute Reset-Command (Fault reset).
Possible Causes Solutions
An unknown hard- or software error has occurred. Disconnect the power supply module from the mains
(including the 24 V power supply) and start a new
attempt. If this error occurs repeatedly, please call
the Beckhoff support that is responsible for you.
Internal: 0x2383, Phase U current offset out of range