Diagmessages of module AxisMain
Multi axis servo system - AX8000120
Version: 1.1
6.21 6183, Internal Watchdog Error
Diagnostic Code (Hex.) Diagnostic Code (Dez.)
6183 24963
Class Type
Error Error
Standard Reaction Reset
Closed loop ramp Execute Reset-Command (Fault reset).
Possible Causes Solutions
To much objects in the PDO-mapping. Check the number of objects in the PDO-mapping.
An unknown hard- or software error has occurred. Disconnect the power supply module from the mains
(including the 24 V power supply) and start a new
attempt. If this error occurs repeatedly, please call
the Beckhoff support that is responsible for you.
Internal: 0x6183, Internal Watchdog Error