Diagmessages of module DeviceMain
Multi axis servo system - AX8000 87
Version: 1.1
4.5 5182, Power supply controlword, live counter inactive
The power supply device controlword contains a live counter which didn't increment for the maximum
accepted timespan.
Diagnostic Code (Hex.) Diagnostic Code (Dez.)
5182 20866
Class Type
Error Error
Standard Reaction Reset
Closed loop ramp Execute Reset-Command (Fault reset).
Possible Causes Solutions
The Power supply status is not alive. Please Check if the Power supply status is linked to
the Supply Device and the Device is in EtherCAT OP
state.