Diagmessages of module AxisMain
Multi axis servo system - AX8000 153
Version: 1.1
6.54 8182, EtherCAT Statemachine shutdown with enabled
Axis
The EtherCAT Statemachine received a shutdown command, while the Axis was enabled.
Diagnostic Code (Hex.) Diagnostic Code (Dez.)
8182 33154
Class Type
Error Error
Standard Reaction Reset
Closed loop ramp Execute Reset-Command (Fault reset).
Possible Causes Solutions
The EtherCAT Statemachine received a shutdown
command, while the Axis was enabled.
Please disable your Axes before Restart or Shutdown
your EtherCAT Master.
Internal: 0x8182, EtherCAT Statemachine shutdown with enabled Axis