6 AUTORECLOSE FUNCTION ALARMS
The following DDB signals will produce an alarm. These are described below.
6.1 AR NO SYS CHECK
The AR No Sys Check
alarm indicates that the system voltages are not suitable for autoreclosing at the end of the
system check time (setting Sys Check Time), leading to a lockout condition. This alarm is latched and must be reset
manually.
6.2 AR CB UNHEALTHY
The AR CB Unhealthy alarm indicates that the CB Healthy input was not ener
gised at the end of the CB Healthy
Time, leading to a lockout condition. This alarm is latched and must be reset manually.
6.3 AR LOCKOUT
The AR Lockout alarm indicates that the device is in a lockout status and that further re-close attempts will not be
made. This alarm can configured to reset automatically (self-reset) or manually as determined by the setting Reset
Lockout by in the CB CONTROL column.
P14x Chapter 13 - Autoreclose
P14xEd1-TM-EN-1 285