6 POWER PROTECTION FUNCTIONS
6.1 OVERPOWER / UNDERPOWER PROTECTION
Pick-up Setting +/- 10%
Reverse/Overpower Drop-off 0.95 x Setting +/- 10%
Low forward power Drop-off 1.05 x Setting +/- 10%
Angle variation pick-up +/- 2°
Angle variation drop-off +/- 2.5°
Operating time +/- 2% or 50 ms, whichever is greater
Repeatability < 5%
Disengagement time <50 ms
tRESET +/- 5%
Instantaneous operating time < 50 ms
6.2 SENSITIVE POWER PROTECTION
Pick-up Setting +/- 10%
Reverse/Overpower Drop-off 0.9 x Setting +/- 10%
Low forward power Drop-off 1.1 x Setting +/- 10%
Angle variation pick-up +/- 2°
Angle variation drop-off +/- 2.5°
Operating time +/- 2% or 50 ms, whichever is greater
Repeatability < 5%
Disengagement time <50 ms
tRESET +/- 5%
Instantaneous operating time < 50 ms
Chapter 23 - Technical Specifications P14x
546 P14xEd1-TM-EN-1