4.3 ADVISORY TEST EQUIPMENT
Advisory test equipment may be required for extended commissioning procedures:
● Current clamp meter
● Multi-finger test plug:
○ P992 for test block type P991
○ MMLB for test block type MML
G blocks
● Electronic or brushless insulation tester with a DC output not exceeding 500 V
● KITZ K-Bus - EIA(RS)232 protocol converter for testing EIA(RS)485 K-Bus port
● EIA(RS)485 to EIA(RS)232 converter for testing EIA(RS)485 Courier/MODBUS/IEC60870-5-103/DNP3 port
● A portable printer (for printing a setting record from the portable PC) and or writeable, detachable memory
device.
● Phase angle meter
● Phase rotation meter
● Fibre-optic power meter.
● Fibre optic test leads (minimum 2). 10m minimum length, multimode 50/125 µm or 62.5µm terminated with
BFOC (ST) 2.5 connectors for testing the fibre-optic RP1 port.
P14x Chapter 21 - Commissioning Instructions
P14xEd1-TM-EN-1 495