32 ADV200 WA • Quick start up guide - Specification and installation
Note! For size 7 only, adaptation for internal mounting of fuses (DC side) on request.
5.1.5 Internal EMC lter
ADV200 WA series inverters are equipped with an internal EMI (except ADV200
WA-...-DC models) lter able to guarantee the performance levels required by EN
61800-3 standard (according to 2nd environment, category C3) with a maximum
of 20 meters of shielded motor cable (up to 50 metres for size 5 and above).