GREE Multi Variable Air Conditioners Indoor Unit
15
Water height difference up to
1.2m,
which can effectively drain out condensing water and save space.
Adopting high-lift DC quiet type drainage pump for lower power consumption and better sound quality;
the maximum lifting height is 1200mm; installation is more flexible and the drainage pipe layout is more
convenient.
4 Specifications
4.1 Low Static Pressure Duct Type Indoor Unit
Model
GMV-ND07PLS/A-T(U)
GMV-ND09PLS/A-T(U)
GMV-ND12PLS/A-T(U)
Product Code
CM810N0080
CM810N0090
CM810N0100
Cooling Capacity
Btu/h
7500
9500
12000
kW
2.2
2.8
3.5
Heating Capacity
Btu/h
9500
10500
13500
kW
2.8
3.1
4
Casing Finish
Galvanized Steel plate
Dimensions
(W×D×H)
Outline
Mm
700×615×200
700×615×200
700×615×200
inch
27-9/16×24-3/16×7-7/8
27-9/16×24-3/16×7-7/8
27-9/16×24-3/16×7-7/8
Packaging
Mm
893×743×305
893×743×305
893×743×305
inch
35-3/16×29-1/4×12
35-3/16×29-1/4×12
35-3/16×29-1/4×12
Net Weight
lbs.
51
51
51
Kg
23
23
23
Gross Weight
lbs.
64
64
64
kg
29
29
29
Pipe
Connection
Liquid Side
mm
Φ6.35
Φ6.35
Φ6.35
inch
Φ1/4
Φ1/4
Φ1/4
Gas Side
mm
Φ9.52
Φ9.52
Φ12.7
inch
Φ3/8
Φ3/8
Φ1/2
Drain Pipe
mm
Φ25
Φ25
Φ25
inch
Φ1
Φ1
Φ1
Power supply
1-phase 208/230V 60Hz
Fan
Type × Quantity
Centrifugal×2
Centrifugal×2
Centrifugal×2
Driving Mechanism
Direct-driven
Motor Type
BLDC
Motor Power Input
W
43
43
43
Motor Running
Current
A
0.3
0.3
0.3
Airflow Rate(H/M/L)
CFM
265/235/147
265/235/147
324/265/206
m
3
/h
450/400/250
450/400/250
550/450/350
External
Static
Pressure
Default
inchW.G
.
0.06
0.06
0.06
Pa
15
15
15
Range
inchW.G
.
0~0.12
0~0.12
0~0.12
Pa
0~30
0~30
0~30
Sound Pressure Level(H/M/L)
dB(A)
31/29/25
31/29/25
32/30/27
Heat Exchanger
Fenestrate plain film --hydrophilic film
Air Filter
PP
Refrigeration Control Device
EXV
Protection Device
Fuse

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-ND07PLS/A-T(U) and is the answer not in the manual?

Gree GMV-ND07PLS/A-T(U) Specifications

General IconGeneral
BrandGree
ModelGMV-ND07PLS/A-T(U)
CategoryAir Conditioner
LanguageEnglish

Related product manuals