GREE Multi Variable Air Conditioners Indoor Unit
17
4.2 Slim Duct Type Indoor Unit
Model
GMV-ND06PLS/B
-T(U)
GMV-ND07PLS/B
-T(U)
GMV-ND09PLS/B
-T(U)
GMV-ND12PLS/B
-T(U)
Product Code
CM810N1980
CM810N1720
CM810N1710
CM810N1700
Cooling Capacity
Btu/h
6000
7500
9500
12000
kW
1.8
2.2
2.8
3.6
Heating Capacity
Btu/h
6000
8500
10500
13500
kW
1.8
2.8
3.2
4
Casing Finish
Galvanized Steel plate
Dimensions
(W×D×H)
Outline
mm
710×462×200
710×462×200
710×462×200
710×462×200
inch
27-15/16×18-3/16
×7-14/16
27-15/16×18-3/16
×7-14/16
27-15/16×18-3/16
×7-14/16
27-15/16×18-3/16
×7-14/16
Packaging
mm
1025×570×285
1025×570×285
1025×570×285
1025×570×285
inch
40-4/16×22-5/16
×10-10/16
40-4/16×22-5/16
×10-10/16
40-4/16×22-5/16
×10-10/16
40-4/16×22-5/16
×10-10/16
Net Weight
lbs.
41
41
41
42
kg
18.5
18.5
18.5
19
Gross Weight
lbs.
52
52
52
53
kg
23.5
23.5
23.5
24
Pipe
Connection
Liquid Side
mm
Φ6.35
Φ6.35
Φ6.35
Φ6.35
inch
Φ1/4
Φ1/4
Φ1/4
Φ1/4
Gas Side
mm
Φ9.52
Φ9.52
Φ9.52
Φ12.7
inch
Φ3/8
Φ3/8
Φ3/8
Φ1/2
Drain Pipe
mm
Φ25
Φ25
Φ25
Φ25
inch
Φ1
Φ1
Φ1
Φ1
Power supply
1-phase 208/230V 60Hz
Fan
Type × Quantity
Centrifugal×2
Centrifugal×2
Centrifugal×2
Centrifugal×2
Driving Mechanism
Direct-driven
Motor Type
BLDC
Motor Power
Input
W
30
30
30
30
Motor Running
Current
A
0.16
0.16
0.16
0.16
Airflow
Rate(H/M/L)
CFM
265/206/118
265/206/118
265/206/118
324/235/177
m
3
/h
450/350/200
450/350/200
450/350/200
550/400/300
External
Static
Pressure
Default
inchW.
G.
0.06
0.06
0.06
0.06
Pa
15
15
15
15
Range
inchW.
G.
0~0.12
0~0.12
0~0.12
0~0.12
Pa
0~30
0~30
0~30
0~30
Sound Pressure Level(H/M/L)
dB(A)
30/25/22
30/25/22
30/25/22
30/25/22
Heat Exchanger
Fenestrate plain film --hydrophilic film
Air Filter
PP
Refrigeration Control Device
EXV
Protection Device
Fuse

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-ND07PLS/A-T(U) and is the answer not in the manual?

Gree GMV-ND07PLS/A-T(U) Specifications

General IconGeneral
BrandGree
ModelGMV-ND07PLS/A-T(U)
CategoryAir Conditioner
LanguageEnglish

Related product manuals