Requirements for Mounting an EX-series Switch on the Desktop or Wall
You can install an EX-series switch on a desktop or wall. When choosing a location,
allow at least 6 in. (15.2 cm) of clearance between the front and back of the chassis
and adjacent equipment or walls.
If you are mounting an EX-series switch on a wall, use the EX-series switch wall
mount kit from Juniper Networks. The wall mount kit is not part of the standard
package and needs to be ordered separately.
Related Topics Clearance Requirements for Airflow and Hardware Maintenance on page 52â–
â– Mounting an EX-series Switch on a Desk or Other Level Surface on page 66
Cabinet Requirements and Specifications for an EX-series Switch
You can mount an EX-series switch on a 19-in. cabinet as defined in Cabinets, Racks,
Panels, and Associated Equipment (document number EIA-310–D) published by the
Electronics Industry Association (http://www.eia.org).
Related Topics Clearance Requirements for Airflow and Hardware Maintenance on page 52â–
â– Rack Requirements and Specifications for an EX-series Switch on page 50
â– Mounting an EX-series Switch on a Rack or Cabinet on page 67
Clearance Requirements
â– Clearance Requirements for Airflow and Hardware Maintenance on page 52
Clearance Requirements for Airflow and Hardware Maintenance
When planning the site for installing an EX-series switch, you must allow sufficient
clearance around the installed switch (see Figure 24 on page 52).
Figure 24: Clearance Requirements for Airflow and Hardware Maintenance
52 â– Requirements for Mounting an EX-series Switch on the Desktop or Wall
Complete Hardware Guide for EX 3200 and EX 4200 Switches