NOTE: EX2200 switches with DC power supply do not provide PoE.
NOTE: For DC power supplies, we recommend that you provide at least 3.5 A
at 48 VDC and use a facility circuit breaker rated for 10 A minimum. Doing so
enables you to operate the switch in any configuration without upgrading
the power infrastructure, and allows the switch to function at full capacity
using multiple power supplies.
Related
Documentation
AC Power Cord Specifications for EX2200 Switches on page 66•
• Power Supply in EX2200 Switches on page 18
• General Safety Guidelines and Warnings on page 155
• General Electrical Safety Guidelines and Warnings on page 179
AC Power Cord Specifications for EX2200 Switches
A detachable AC power cord is supplied with the AC power supplies. The coupler is type
C13 as described by International Electrotechnical Commission (IEC) standard 60320.
The plug at the male end of the power cord fits into the power source outlet that is
standard for your geographical location.
CAUTION: The AC power cord provided with each power supply is intended
for use with that power supply only and not for any other use.
NOTE: In North America, AC power cords must not exceed 4.5 meters
(approximately 14.75 feet) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52 and Canadian Electrical
Code (CEC) Section 4-010(3). The cords supplied with the switch are in
compliance.
Table 24 on page 66 lists AC power cord specifications provided for each country or
region.
Table 24: AC Power Cord Specifications
Plug TypePlug StandardsElectrical SpecificationsCountry/Region
RA/3IRAM 2073250 VAC, 10 A, 50 HzArgentina
SAA/3AS/NZZS 3112250 VAC, 10 A, 50 HzAustralia
BR/3NBR 14136250 VAC, 10 A, 50 HzBrazil