Functional Description Analog In- and Outputs
246
Name: Basis
KEB COMBIVERT F5
Chapter Section Page Date
04.05.04
© KEB Antriebstechnik, 2002
All rights reserved
X2A.
123456789
R = 3...10 kW
PE
0...10V DC
Ri=30k
(An.0 / An.10 = 0)
6.2.2 Interface Selection
(An.0; An.10)
Fig. 6.2.2.a Connection as differential voltage inputs 0...±10V DC
The output CRF Kl. X2A.7 may
be loaded with maximal 6mA!
Depending on the selected interface (An.0/An.10) the analog inputs AN1 and AN2
can process following input signals:
An.0 / An.10= 0 0...±10 V (default)
= 1 0...±20 mA
= 2 4...20 mA
Fig. 6.2.2.b Control with potentiometer and internal reference voltage
X2A.
123456789
PE
0...±10 VDC
+-
SPS
+-
SPS
1)
1) Connect equipotential bonding conductor only, if a potential difference of >†30V
exists between the controls. The internal resistance is reduced to 30 kOhm.
X2A.
123456789
+
0...±20 mADC
4...20 mADC
Ri = 250
PE
+
An.0 / An.10 = 1 or 2
Fig. 6.2.2.c Control with current signal
Interface Selection
(An.20)
With An.20 it is determined from where the 3. analog setpoint signal is received.
Following values can be defined:
Value Function
0 Analog value from the optional analog input (default)
1 Analog value via the terminals of AN1
Ri = 55 kOhm

Table of Contents

Other manuals for KEB COMBIVERT F5 Servo

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Servo and is the answer not in the manual?

KEB COMBIVERT F5 Servo Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5 Servo
CategoryDC Drives
LanguageEnglish

Related product manuals