6 12
KEB COMBIVERT F5
10
Name: Basis
04.05.04
Chapter Section Page Date
© KEB Antriebstechnik, 2002
All rights reserved
Functional Description Technology Control
Parameter Addr.
min
max
default
[?] Notes
cn 0 PID reference source 0700 X X – 0 4 1 0 – –
cn 1 PID abs. reference 0701 X X – -400,0 400,0 0,1 0,0 % –
cn 2 PID act. value source 0702 X X – 0 7 1 0 – –
cn 3 PID abs. act. value 0703 X – – -400,0 400,0 0,1 0,0 % –
cn 4 PID kp 0704 X X – 0,00 250,00 0,01 0,00 – –
cn 5 PID ki 0705 X X – 0,000 30,000 0,001 0,000 – –
cn 6 PID kd 0706 X X – 0,00 250,00 0,01 0,00 – –
cn 7 PID pos. limit 0707 X X – -400,0 400,0 0,1 400,0 % –
cn 8 PID neg. limit 0708 X X – -400,0 400,0 0,1 -400,0 % –
cn 9 PID fading time 0709 X X – -0,01 300,00 0,01 0,00 s -0,01 freq. dependend
cn10 PID reset condition 070A X X – 0 2 1 0 – –
cn11 PID reset inp. sel. 070B X – X 0 4095 1 0 – –
cn12 I reset inp. sel. 070C X – X 0 4095 1 0 – –
cn13 fade in reset inp. sel. 070D X – X 0 4095 1 0 – –
cn14 PID out freq at 100% 070E X X – -400,0 400,0 0,0125 0 Hz dependend on ud.2
ru13 Actual utilization 020D – – – 0 255 1 0 % –
ru17 Active current 0211 – – – -3276,7 3276,7 0,1 0 A –
ru18 Actual DC voltage 0212 – – – 0 1000 1 0 V –
ru28 AN1 post amplifier display 021C – – – -400,0 400,0 0,1 0 % –
ru30 AN2 post amplifier display 021E – – – -400,0 400,0 0,1 0 % –
ru53 AUX display 0235 – – – -400,0 400,0 0,1 0 % –
6.12.5 Used Parameters