3
HardwareControl Cards
3
15
KEB COMBIVERT F5-M / S
Name: Basis
18.05.04
Section PageDate
© KEB Antriebstechnik, 2002
All Rights reserved
Chapter
3.1.4 Terminal strip X2A
PIN Function Name Description
1 + Set Value input 1 AN1+ The input signal (0...±10 V; 0...±20 mA and 4...20 md is determined
2 - Set Value input 1 AN1- with An.0 / 10. Specification and control see chap. 6.2.2.
3 + Set Value input 2 AN2+ Resolution: 12 Bit, Ri = 30 kΩ, Scan time: 1 ms /
4 - Set Value input 2 AN2- at fast setpoint input: 250 µs (see chapter 6.4.2)
5 Analog Output 1 ANOUT1 The variable for outputting at analog output 2 is determined with
An.31 / 36. Specification and control see chap. 6.2.8.
6 Analog Output 2 ANOUT2 Voltage range: 0...±10V, Ri = 100 Ω, Resolution: 12 Bit
PWM frequency: 3,4 kHz, filter response 1. order: 178 Hz
7 +10 V Output CRF Reference voltage output +10 VDC +5% / max. 4 mA for set value
potentiometer.
8 Analog Mass COM Mass for analog in- and outputs
9 Analog Mass COM Mass for analog in- and outputs
10 Progr. Input 1 I1 Specifications, control und programming of the digital
11 Progr. Input 2 I2 inputs see chapter 6.3
12 Progr. Input 3 I3 All digital inputs are free programmable.
13 Progr. Input 4 I4 The control release is firmly linked with the input ST, but can be
14 Progr. Input Forward F additional occupied with other functions.
15 Progr. Input Reverse R Ri = 2,1 kΩ
16 Progr. Input Control Rel. ST Scan time: 1 ms
17 Progr. Input Reset RST
18 Transistor Output 1 O1 Specifications, control und programming of the digital
19 Transistor Output 2 O2 transistor outputs see chap. 6.3.12...6.3.22,
a total of max. 50 mADC for both outputs
20 +24 V Output U
out
approx. 24V DC output (max.100 mA)
21 20...30 V Input U
in
Ext. supply voltage for digital in-/outputs, potential 0V (X2A.22/23)
22 Digital Mass 0V Potential for digital in-/outputs
23 Digital Mass 0V Potential for digital in-/outputs
24 Relay 1 /NO contact RLA Programmable relay output 1 (Terminal X2A.24...26);
25 Relay 1 /NC contact RLB Programmable relay output 2 ( Terminal X2A.27...29)
26 Relay 1 /switching contact RLC Specifications, control und programming of the relay outputs
27 Relay 2 /NO contact FLA see chapter 6.3.11...6.3.17
28 Relay 2 /NC contact FLB max. 30 V DC, 1 A
29 Relay 2 /switching contact FLC
123456789
10 11 12 13 14 15 16 17 18 19 20 21
22 23 24 25 26 27 28 29