CP - ParameterOperation
4
3
KEB COMBIVERT F5-M / S8
Name: Basis
17.05.04
Chapter Section Page Date
© KEB Antriebstechnik, 2003
All Rights reserved
4.3.5 Basic Adjustment
of the Drive
Intermediate circuit voltage
Display of actual DC-link voltage in volt.
Typical calues:
Intermediate circuit voltage /
Peak value
Output voltage
CP.8 makes it possible to recognize short-time voltage rises within an operating cycle.
For that the highest value of CP.7 is stored in CP.8. The peak value memory can be
cleared by pressing the UP, DOWN or ENTER key or over bus by writing any value
you like to the address of CP.8. The switch off of the inverter also clears the memory.
Display of the actual output voltage in volt.
Speed control / Configuration With this parameter the basic setting of the speed controller is determined.
Adjustment range: F5-M: 0(off)...63 / F5-S: 4...5
Resolution: 1
Factory setting: F5-M: 0 (off) / F5-S: 4
Value Function
0 off (controlled operation)
1 -reserved-
2 -reserved-
3 off (controlled operation)
4 Speed control (regulated operation)
5 Torque control (regulated operation)
The following parameters determine the fundamental operating data of the drive and
must be adjusted for the initial commissioning (see chapter 4 ÑStart-upì). They should
be checked and/or adapted to the application.
V-class normal operation over voltage (E.OP) under voltage (E.UP)
230 V 300Ö330 V DC ca. 400 V DC ca. 216 V DC
400 V 530Ö620 V DC ca. 800 V DC ca. 240 V DC