Functional Description Analog In- and Outputs
266
Name: Basis
KEB COMBIVERT F5
Chapter Section Page Date
04.05.04
© KEB Antriebstechnik, 2002
All rights reserved
-10%
10%
10%
-10%
6.2.6 Zero Point Hyste-
resis (An.4;
An.14; An.24)
Through capacitive as well as inductive coupling on the input lines or voltage fluctuations
of the signal source, the motor connected to the inverter can still drift (tremble) during
standstill in spite of the analog input filter. It is the task of the zero point hysteresis to
suppress this.
With the parameters An.4 / 14 / 24 the respective analog signals can be faded out
within a range of 0...10% . The adjusted value is applicable for both directions of
rotation.
If a negative percent value is adjusted the hysteresis acts in addition to the zero point
around the current setpoint. Setpoint changes are accepted only if they are larger than
the adjusted hysteresis.
from interference
suppression filter
for the further signal processing
fade-out range
Input Parameter Value range Resolution Default value
AN1 An.4 0...±10% 0,1% 0,2%
AN2 An.14 0...±10% 0,1% 0,2%
AN3 An.24 0...±10% 0,1% 0,2%
Fig. 6.2.6 Zero point hysteresis
Value range
Bit -No. Decimal value Input Terminal
0 1 ST (prog. input Ñcontrol release/Resetì) X2A.16
1 2 RST (prog. input ÑResetì) X2A.17
2 4 F (prog. input Ñforwardì) X2A.14
3 8 R (prog. input Ñreverseì) X2A.15
4 16 I1 (prog. input 1) X2A.10
5 32 I2 (prog. input 2) X2A.11
6 64 I3 (prog. input 3) X2A.12
7 128 I4 (prog. input 4) X2A.13
8 256 IA (internal input A) none
9 512 IB (internal input B) none
10 1024 IC (internal input C) none
11 2048 ID (internal input D) none
Input selection table