CP - ParameterOperation
4
3
KEB COMBIVERT F5-M / S4
Name: Basis
17.05.04
Chapter Section Page Date
© KEB Antriebstechnik, 2003
All Rights reserved
The following lists shows the CP-parameter groups of F5-MULTI and F5-SERVO
predefined by us. The definition of the CP-parameters is done in the User-Definition-
Parameters (ud). How you can define your own parameters is described in Chapter
6.12.
4.3.2 Factory Setting
F5-MULTI:
CP.0 password 0...9999 1 - - - ud.1
CP.1 encoder 1 speed ±4000 0,125 0 rpm - ru.9
CP.2 set value display ±4000 0,125 0 rpm - ru.1
CP.3 inverter state 0...255 1 0 - - ru.0
CP.4 apparent current 0...6553,5 0,1 0 A - ru.15
CP.5 peak apparent current 0...6553,5 0,1 0 A - ru.16
CP.6 actual torque display ±10000,00 0,01 0 Nm - ru.12
CP.7 actual DC voltage 0...1000 1 0 V - ru.18
CP.8 peak DC voltage 0...1000 1 0 V - ru.19
CP.9 output voltage 0...778 1 0 V - ru.20
CP.10 speed control config. 0...5 1 0 - - cs.0
CP.11 DASM rated speed 0...64000 1 LTK rpm - dr.1
CP.12 DASM rated frequency 0,0...1600,0 0,1 LTK Hz - dr.5
CP.13 DASM rated current 0,0...710 0,1 LTK A - dr.0
CP.14 DASM rated voltage 120...500 1 LTK V - dr.2
CP.15 DASM rated cos(phi) 0,50...1,00 0,01 LTK - - dr.4
CP.16 DASM rated power 0,35...400,00 0,01 LTK kW - dr.3
CP.17 load mot.dependent parameter 1...2 1 1 - E fr.10
CP.18 boost 0,0...25,5 0,1 LTK % - uf.1
CP.19 rated frequency 0...400 0,0125 50 Hz - uf.0
CP.20 encoder 1 (inc/r) GBK...GBK 1 GBK inc - ec.1
CP.21 enc.1 rotation 0...19 1 0 - - ec.6
CP.22 max. reference forward 0...4000 0,125 2100 rpm - op.10
CP.23 step value 1 ±4000 0,125 100 rpm - op.21
CP.24 step value 2 ±4000 0,125 -100 rpm - op.22
CP.25 acc. time forward 0,00...300,00 0,01 5,00 s - op.28
CP.26 dec. time forward -0,01...300,00 0,01 5,00 s - op.30
CP.27 s-curve time acc. for. 0,00...5,00 0,01 0,00 s - op.32
CP.28 torque reference source 0...5 1 2 - E cs.15
CP.29 absolute torque ref ±10000,00 0,01 LTK Nm - cs.19
CP.30 KP speed 0...32767 1 300 - - cs.6
CP.31 KI speed 0...32767 1 100 - - cs.9
CP.32 switching frequency 2/4/8/12/16 - LTK kHz E uf.11
CP.33 Relais output 1 condition 0...74 1 4 - E do.2
CP.34 Relais output 2 condition 0...74 1 2 - E do.3
CP.35 proh. rot. stopping mode 0...6 1 6 - - pn.7
CP.36 E. EF stopping mode 0...6 1 0 - - pn.3
LTK: depending on power circuit