EasyManuals Logo
Home>KEB>DC Drives>COMBIVERT F5 Servo

KEB COMBIVERT F5 Servo User Manual

KEB COMBIVERT F5 Servo
378 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #244 background imageLoading...
Page #244 background image
6 9
KEB COMBIVERT F5
12
Name: Basis
04.05.04
Chapter Section Page Date
© KEB Antriebstechnik, 2002
All rights reserved
Functional Description Special Functions
According to following table the inputs with which the timer is reset can be specified.
The individual inputs are OR-operated, i.e. if one of the specified inputs is triggered,
the timer jumps back to zero. If a starting and reset condition are active simultaneously,
reset has prioritiy.
Input selection / Timer Reset
(LE.19/24)
Timer start Input selection
(LE.17/22)
Additionally the timer can be activated by one or several inputs. The sum of the
valences is to be entered, if the timer shall be started by different inputs. The individual
inputs are OR-operated.
ru.43 / ru.44 displays the actual counter reading dependend of the adjusted clock
source (LE.21/26). By writing on ru.43/44 the counter can be set to a value. If the
clock source is changed during the running time the counter content is maintained but
is interpreted according to the new clock source.
Current counter content
(ru.43/44)
Bit -No. Decimal value Input Terminal
0 1 ST (prog. input „control release/Reset“) X2A.16
1 2 RST (prog. input „Reset“) X2A.17
2 4 F (prog. input „forward“) X2A.14
3 8 R (prog. input „reverse“) X2A.15
4 16 I1 (prog. input 1) X2A.10
5 32 I2 (prog. input 2) X2A.11
6 64 I3 (prog. input 3) X2A.12
7 128 I4 (prog. input 4) X2A.13
8 256 IA (internal input A) none
9 512 IB (internal input B) none
10 1024 IC (internal input C) none
11 2048 ID (internal input D) none
Bit -No. Decimal value Input Terminal
0 1 ST (prog. input „control release/Reset“) X2A.16
1 2 RST (prog. input „Reset“) X2A.17
2 4 F (prog. input „forward“) X2A.14
3 8 R (prog. input „reverse“) X2A.15
4 16 I1 (prog. input 1) X2A.10
5 32 I2 (prog. input 2) X2A.11
6 64 I3 (prog. input 3) X2A.12
7 128 I4 (prog. input 4) X2A.13
8 256 IA (internal input A) none
9 512 IB (internal input B) none
10 1024 IC (internal input C) none
11 2048 ID (internal input D) none
From the following table the conditions can be selected at which the timer is started.
The individual conditions are OR-operated.
Bit Value Timer / Starting condition
0 1 Modulation on
1 2 Modulation off
2 4 Actual freq. =setpoint freq.
In case of several starting conditions the values are to be added up.
Timer / Starting condition
(LE.18/23)

Table of Contents

Other manuals for KEB COMBIVERT F5 Servo

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Servo and is the answer not in the manual?

KEB COMBIVERT F5 Servo Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5 Servo
CategoryDC Drives
LanguageEnglish

Related product manuals