6.2.2 Examples
6.2.2.1 Parameter reading
The heatsink temperature (43 °C) C061 is to be read from the controller using address 5 and
parameter channel 1.
Identifier calculation
Identifier parameter channel 1 to controller = 1536 + controller address
Identifier = 1536 + 5 = 1541
Command read request (request to read a parameter from the drive
Command =40
hex
Index calculation
Index = 24575 - code number - 2000 (PS - 1) Index = 24575 - 61 - 2000 ú 0 = 24514 = 5FC2
hex
Telegram to drive:
Identifier Command Index Low
Byte
Index High
Byte
Subindex Data 1 Data 2 Data 3 Data4
1541 40
hex
C2
hex
5F
hex
00 00 00 00 00
Telegram from drive
Identifier:
Parameter channel 1 of controller (=1408) + controller address = 1413
Command:
Read response to read request with the current value of 43
hex
Index of read request
5FC2
hex
Subindex:
0
Data1toData4:
43 °C
S 10.000 = 430.000 = 00 06 8F B0
Identifier Command Index Low
Byte
Index High
Byte
Subindex Data 1 Data 2 Data 3 Data4
1413 43
hex
C2
hex
5F
hex
00 B0
hex
8F
hex
06
hex
00
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 2175 and is the answer not in the manual?

Lenze 2175 Specifications

General IconGeneral
BrandLenze
Model2175
CategoryNetwork Hardware
LanguageEnglish